Optimasi Profil Tegangan Sistem Distribusi 6-Bus Menggunakan Kapasitor Bank Berbasis ETAP 19.0.1

Authors

  • Mulia Parlaungan Hsb Universitas Negeri Medan
  • Taufiq Akbar Alghazali Universitas Negeri Medan
  • Arwadi Sinuraya Universitas Negeri Medan
  • Desman Jonto Sinaga Universitas Negeri Medan

DOI:

https://doi.org/10.61722/jipm.v3i6.1635

Keywords:

load flow, undervoltage, capacitor bank, ETAP, OCP

Abstract

This study analyzes the load flow of a 6-bus distribution system using ETAP 19.0.1 software. The initial load flow simulation revealed undervoltage conditions on certain buses, particularly bus 5 and bus 6, which were below the IEEE standard. To address this issue, the Optimal Capacitor Placement (OCP) feature was applied, recommending capacitor installations of 629 kVar on bus 4 and 1338 kVar on bus 6. The post-installation simulation results showed voltage improvements across all buses, bringing them within the IEEE standard range (0.95 ≤ Vb ≤ 1.05 pu). Therefore, capacitor bank installation is proven to be effective in improving voltage profiles and enhancing power quality in the distribution system.

References

A. Hisyam dan Purwoharjono, “Peningkatan Profil Tegangan Menggunakan Kapasitor Bank Pada Jaringan Teganagan Menangah (JTM) 20 kV Penyulang Sei Deras,” J. Tek. Elektro UNTAN, vol. 8, hal. 1–8, 2022.

D. M. Ahmad Muntaha1*, Indra Darmawan2, Ahmad Jaya3, “SIMULASI PERBAIKAN DROP TEGANGAN DAN SUSUT PADA GARDU INDUK ALAS DENGAN PENAMBAHAN KAPASITOR BANK Ahmad,” hal. 197–212, 2025.

P. Abidin, “Penempatan Optimal Kapasitor Bank pada Jaringan Distribusi 20 kV menggunakan ETAP 7.5.0,” Semin. Nas. Teknol. Informasi, Komun. dan Ind., no. September, hal. 6, 2014.

H. Ariwata, N. P. Agustini, dan R. Setiawan, “OPTIMALISASI PENEMPATAN KAPASITOR UNTUKMENINGKATKAN PROFIL TEGANGAN PADA JARINGANDISTRIBUSI 20 kV,” Semin. Nas. Fortei7-6, vol. 5, no. 1, hal. 52–58, 2024.

M. D. Prasetyo, S. T. Elektro, F. Teknik, dan U. N. Surabaya, “Analisis Pemasangan Kapasitor Bank Terhadap Perubahan Nilai Faktor Daya Dan Jatuh Tegangan Pada Unit Power Plant Di Pusat Pengembangan Sumber Daya Manusia Minyak Dan Gas Bumi Cepu Subuh Isnur Haryudo , Joko , Achmad Imam Agung,” J. Tek. Elektro, vol. 11, hal. 208–217, 2022.

Downloads