Evaluasi Kondisi Tahanan Isolasi House Service Transformer Pada Power Station PLTA Peusangan
DOI:
https://doi.org/10.61722/jipm.v3i6.1637Keywords:
Insulation Resistance; Polarization Index; TransformerAbstract
This study aims to evaluate the condition of the House Service Transformer (HST) insulation at No. 1 Power Station PLTA Peusangan during the pre-operational stage. The testing was conducted directly in the field using a Megger Insulation Tester MIT 525 with a DC voltage of 5 kV on the HV side and 1 kV on the LV side to obtain the Insulation Resistance (IR) values in the HV–LV, HV–ground, and LV–ground configurations, as well as the Polarization Index (PI) on the HV-LV side. The IR measurement results were 42.2 GΩ, 17.43 GΩ, and 5.45 GΩ at a temperature of 36.0 °C and humidity of 95.3%, all of which were well above the minimum reference limit of 100 MΩ. The PI value obtained was 1.20, which was interpreted with caution because the insulation resistance in the first minute was already in the order of gigaohms, so PI was more appropriately positioned as a supporting parameter. Overall, the test results showed that the HST insulation system was still in very good condition and suitable to support the operational readiness of the internal electrical system of the hydroelectric power plant.
References
Ardito, A., & Waluyo. (2024). Analisis Kondisi Isolasi Generator Unit 2 PT Indonesia XYZ Menggunakan Metode Pengujian Insulation Resistance dan Polarity Index. 1–13.
Chapman, J. S. (2012). Electrical Machinery Fundamental 5th Edition. Mc Graw Hill.
Corio, D., Maulana, R., Yunesti, P., & Hendri, Z. (2023). Perencanaan dan Operasi Perencanaan dan Operasi Sistem Tenaga Listrik. ITERA Press.
Flanagan, W. M. (1993). Handbook of Transformer Design & Applications (p. 237). McGraw-Hill.
IEEE-SA. (2013). IEEE Std 43-2013 Recommended Practice for Testing Insulation Resistance of rotating machinery. In Institute of Electrical and Electronics Engineers.
Indra, M. H., Yanolanda, S. H., & Priyadi, I. (2022). Pengujian Tahanan Isolasi Pada Transformator Distribusi 160 kVA Di PT. PLN (PERSERO) UP3 Bengkulu. Jurnal Amplifier : Jurnal Ilmiah Bidang Teknik Elektro Dan Komputer, 12(2).
Kulkarni, S. V, & Khaparde, S. A. (2013). Transformer Engineering: Design, Technology, and Diagnostics, Second Edition. CRC Press.
Manual Book Insulation Resistance Testers. (n.d.). Megger. www.b2bcompliance.org.uk
Prima, G. A., Anthony, Z., & Anugrah, A. (2023). Analisa Tahanan Isolasi Pada Transformator Daya 150/30 KV Gardu Induk Padang Luar PT PLN (Persero) Bukittinggi. Indonesian Journal of Engineering and Technology (INAJET), 6, 23–33.
Rafiansyah, M. A., & Arief Wisaksono. (2022). Analisis Uji Tahanan Isolasi Pada Power Transformer PT. PQR. Jurnal Cakrawala Ilmiah, 1(11), 2723–2732.
Siburian, M. ., & Buulolo, J. T. M. (2021). Studi Analisis Ketahanan Isolasi Pada Transformator Di Gardu Induk Labuhan. Jurnal Darma Agung, 29(3), 499–510.
Suganda, A. M. (2021). Analisa Kualitas Tahanan Isolasi Transformator Daya. Program Studi Teknik Elektro - ISTN, 23(2).
Sutjipto, R., Mukti, H. K., & Dzulfiqar, K. E. (2024). Analisis Kondisi Isolasi Pada Station Service Transformer (SST). ELPOSYS: Jurnal Sistem Kelistrikan, 20.
Winders, J. J. (2002). Power Transformers Principles and Applications. In Marcel Dekker, Inc.
Yusniati, Pelawi, Z., Armansyah, & Taufik, I. (2021). Pengukuran Resistansi Isolasi Instalasi Penerangan Basement Pada Gedung Rumah Sakit Grand Mitra Medika Medan. Buletin Utama Teknik, 16(3), 240–247.
Downloads
Published
How to Cite
Issue
Section
License
Copyright (c) 2025 JURNAL ILMIAH PENELITIAN MAHASISWA

This work is licensed under a Creative Commons Attribution-ShareAlike 4.0 International License.